. Fault tracing lists the warning and fault messages with the possible causes and remedies. Analogue Extension Module, describes the communication between the drive. Fault 64 - Drive OverLoad - Drive rating of 110% for 1 minute or 150% for 3 seconds has been exceeded. Fault 49 - Drive Powerup - No fault displayed. Used as a Power Up Marker in the Fault Queue indicating that the drive power has been cycled.

Restricted Earth Fault

Disable Danfoss Drive Earth Fault Parameter

Disable Danfoss Drive Earth Fault Parameter List

Hi to all. I have noticed some tripping of a Danfoss inverter VLT5000 with alarm 14 EARTH FAULT. After recycling the power and resetting the inverter it resumes normal operation. Is there any logical explanation for this ? Earth fault is a short circuit between phase and earth and is something more or less permanent. Should i suspect the screnned cable between inverter and motor or should i expect a possible motor insulation failure ?
Thanks in advance for your time.